5V 3A, 12V 1.67A, 15V 1.34A, 24V 1A Single Output Industrial DIN Rail Power Supply 20W





|
SPECIFICATIONS |
||||
|
OUTPUT |
|
|||
|
Model |
HT-MDR-20-5 |
HT-MDR-20-12 |
HT-MDR-20-15 |
HT-MDR-20-24 |
|
DC Voltage |
5V |
12V |
15V |
24V |
|
Rated Current |
3A |
1.67A |
1.34A |
1A |
|
Current Range |
0-3A |
0-1.67A |
0-1.34A |
0-1A |
|
Rated Power |
15W |
20W |
20W |
24W |
|
Ripple & Noise |
80mVp-p |
120mVp-p |
120mVp-p |
150mVp-p |
|
Voltage Tolerance |
±2% |
±1% |
±1% |
±1% |
|
Line regulation |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
|
Load regulation |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
|
Setup, Rise Time |
500ms,30ms/230VAC 1000ms,30ms/115VAC at full load |
|||
|
Hold Up Time |
50ms/230VAC 25ms/115VAC at full load |
|||
|
|
|
|||
|
INPUT |
|
|||
|
Voltage Range |
85-264VAC 47-63Hz; 120-370VDC |
|||
|
AC Current |
0.55A/115VAC 0.35A/ 230VAC |
|||
|
Efficiency |
76% |
80% |
81% |
84% |
|
Inrush Current |
Cold start 20A/115V 40A/230V |
|||
|
Leakage Current |
<1mA/240VAC |
|||
|
|
|
|||
|
PROTECTION |
|
|||
|
Over Load |
105% - 160% rated output power |
|||
|
Protection type: Constant current limiting, recovers automatically after fault condition is removed |
||||
|
Over Voltage |
5.75-6.75V |
13.8-16.2V |
17.25-20.25V |
27.6-32.4V |
|
Protection type: Shut down o/p voltage, re-power on to recover |
||||
|
|
|
|||
|
ENVIRONMENT |
|
|||
|
Working Temp., Humidity |
-20~+70deg; 20%~90% RH non-condensing |
|||
|
Storage Temp., Humidity |
-40~+85deg; 10%~95%RH |
|||
|
Temp. Coefficient |
±0.03%/deg(0~50deg) |
|||
|
Vibration |
10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes |
|||
|
|
|
|||
|
SAFETY |
|
|||
|
Withstand Voltage |
I/P-O/P: 3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC |
|||
|
Isolation Resistance |
I/P-O/P, I/P-FG, O/P-F/G: 100M Ohms / 500VDC/25deg/70% RH |
|||
|
|
|
|||
|
STANDARD |
|
|||
|
Safety Standard |
Design refer to UL508,TUV EN60950-1 |
|||
|
EMC Standard |
Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-1, EN61204-3, light industry level, criteria A |
|||
|
|
|
|||
|
OTHERS |
|
|||
|
Dimension |
22.5*90*100mm(W*H*D) |
|||
|
Weight |
0.19Kg |
|||
|
Packing |
72pcs/carton/14.7kg/0.91CUFT |
|||
|
|
|
|||
|
NOTE |
|
|||
|
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25deg of ambient temperature. 2.Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor. 3.Tolerance: includes set up tolerance, line regulation and load regulation. 4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |
||||